24 – 6
24.3.1 Removing arc chutes
A Frame size I and II with flush arc chute
B F
rame size II, C-class and frame size III
1 T
urn out the screw about 15 mm, don't take it out;
FS III and FS II, C-class:
turn out the screw completly
2 P
ush the cover back;
FS III and FS II, C-class: lift the cover carefully
3 R
emove the cover
4 T
ake out the arc chute
5 Pus
h the intermediate unit back and remove it
24.3.2 Visual inspection
In the case of heavy wear (burnout on arc splitter plates), replace
the circuit breaker.
24.3.1 Lichtbogenkammer ausbauen
A Baugröße I und II mit niedriger Lichtbogenkammer
B Baug
röße II, C-Klasse und Baugröße III
1 Schr
aube ca. 15 mm herausdrehen, nicht herausnehmen;
BG III und BG II, C-Klasse:
Schraube komplett herausdrehen
2 Dec
kel zurückschieben;
BG III und BG II, C-Klasse: Deckel vorsichtig anheben
3 Dec
kel abnehmen
4 L
ichtbogenkammer herausnehmen
5 Z
wischenteil nach hinten schieben und herausnehmen
24.3.2 Sichtprüfung vornehmen
Bei starkem Verschleiß (Ausbrennungen an den Löschblechen) Lei-
stungsschalter erneuern.
VORSICHT CAUTION
Bruchgefahr!
Lichtbogenkammer nicht senkrecht auf die Isolierwände
a
bstellen, sondern auf die Seite legen.
Risk of breaking!
Do not place the arc chute vertically on the insulating walls,
but lay it on the side.
PH 2
0
0
4
3
-
0
1
2
1
3
4
B
5
0042_nu
1
2
4
A

Table of Contents