A-8
Setting Alarm Reset/Inhibit Timer
Overview The Alarm Reset/Inhibit Timer system option disables the Alarm Silence and System Reset
keys for a user-definable duration that ranges from 1 to 60 minutes. The timer is activated only
by the first alarm (i.e., subsequent alarms do not reset the timer).
Note: The default setting is not enabled. This option must be enabled for Canadian jobs
Enabling Alarm
Reset/Inhibit
Timer
To enable the Alarm Reset/Inhibit Timer, do the following:
1. Click on the Panel tab at the top of the programmer.
2. Click on the System Options tab at the bottom of the programmer. A screen similar to the
one shown below appears.
3. Click on the checkbox to the right of Alarm Silence/Reset Inhibit. Specify the timer value in
the Seconds box to the right of the checkbox.
Figure A-8. The Panel: System Options tab