A-7
Setting alarm verification timer to Canadian operation
Introduction When you select Canadian operation for the alarm verification feature, the system operates as
follows:
If a point specified within one of the alarm verification lists enters an alarm state, the
system delays the annunciation of the alarm for 15 seconds.
When the 15-second timer expires, the system attempts to reset the initiating device for
five seconds.
After the five-second timer expires, the system evaluates the state of the initiating device
for 10 additional seconds. After 10 seconds, if the device is still in alarm, the system
immediately annunciates the alarm.
Procedure 1. Click on the List tab to display the List window.
2. At the bottom of the List window, select the Alarm Verification tab.
3. Right-click on one of the lists and select Properties. The Alarm Verification Properties
dialog shown below appears.
4. Click on the Alarm Verification tab.
5. Click on the drop down list box and select Canadian (ULC).
Setting this property for one alarm verification list sets it for all lists.
Figure A-7. Alarm verification properties: Alarm Verification tab

Table of Contents

Other manuals for Simplex 4010ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010ES and is the answer not in the manual?

Simplex 4010ES Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Operating Temperature32°F to 120°F (0°C to 49°C)
Power Supply120V AC or 240V AC
Zones10
Communication PortsRS-232, Ethernet
Signaling Line Circuits (SLCs)2
Notification Appliance Circuits (NACs)4
Max Notification AppliancesVaries based on NAC configuration and power supply
Communication OptionsCellular, Ethernet
Weight30 lbs
Humidity RangeUp to 93% non-condensing
CertificationsUL, FM, CSFM, MEA