EasyManua.ls Logo

Stober PS6A34 - 13.3.15 Event 46: Low Voltage

Stober PS6A34
264 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
STOBER 13 | Diagnostics
02/2019 | ID 442728.05
195
13.3.15 Event 46: Low voltage
The possible effects depend on the configured level (U00):
§ 0: Inactive
§ 1: Message
§ 2: Warning
§ 3: Fault
The drive controller is interrupted if:
§ A29 = 0: Inactive for STOBER device controller
or
§ A540 = 0: disable drive, motor is free to rotate for CiA device controller
Response:
§ The power unit is disabled and axis movement is no longer controlled by the drive controller
§ The brakes are no longer controlled by the drive controller and engage in the event of an
inactive release override (F06)
The drive controller is interrupted with a quick stop if:
§ A29 = 1: Active for STOBER device controller
or
§ A540 = 2: slow down on quick stop ramp for CiA device controller
Response:
§ The axis is stopped by a quick stop; meanwhile, the brakes are controlled by the drive
controller and remain released
§ At the end of the quick stop, the power unit is disabled and axis movement is no longer
controlled by the drive controller; the brakes are no longer controlled by the drive controller
and engage in the event of an inactive release override (F06)
Cause Check and action
Supply voltage does not
correspond to the configured
supply voltage
Check the supply voltage, parameterized supply voltage and
undervoltage limit and correct them if necessary (A36, A35)
Supply voltage below
undervoltage limit
Check undervoltage limit and correct it if necessary (A35)
Tab. 198: Event 46 – Causes and actions

Table of Contents

Related product manuals