STOBER 13 | Diagnostics
02/2019 | ID 442728.05
223
13.3.40 Event 88: Control panel
The drive controller is interrupted if:
§ A29 = 0: Inactive for STOBER device controller
or
§ A540 = 0: disable drive, motor is free to rotate for CiA device controller
Response:
§ The power unit is disabled and axis movement is no longer controlled by the drive controller
§ The brakes are no longer controlled by the drive controller and engage in the event of an
inactive release override (F06)
The drive controller is interrupted with a quick stop if:
§ A29 = 1: Active for STOBER device controller
or
§ A540 = 2: slow down on quick stop ramp for CiA device controller
Response:
§ The axis is stopped by a quick stop; meanwhile, the brakes are controlled by the drive
controller and remain released
§ At the end of the quick stop, the power unit is disabled and axis movement is no longer
controlled by the drive controller; the brakes are no longer controlled by the drive controller
and engage in the event of an inactive release override (F06)
Cause Check and action
Commissioning and
parameterization computer
heavily loaded
Check the number of open windows (DS6) and the number of active
programs and reduce the number if necessary
Connection error Check the connection and correct it if necessary
Defective network cable Check the cable and replace it if necessary
Faulty network connection Check the network settings and, if applicable, the switch, router or
wireless connections and correct them or contact your network service
provider if necessary
Tab. 223: Event 88 – Causes and actions