STOBER 10 | Commissioning
05/2019 | ID 442790.01
117
10.1 Initiating the project
In order to be able to configure all drive controllers and axes of your drive system using DriveControlSuite, you must record
them as part of a project.
10.1.1 Projecting the drive controller and axis
Create a new project and project the first drive controller along with the accompanying axis.
Creating a new project
1. Start DriveControlSuite.
2. Click Create new project.
ð The project configuration window opens and the Drive controller button is active.
Projecting the drive controller
1. Properties tab:
Establish the relationship between your circuit diagram and the drive controller to be projected in DriveControlSuite.
Reference: Specify the reference code (equipment code) of the drive controller.
Designation: Give the drive controller a unique name.
Version: Version your project configuration.
Description: If necessary specify supporting additional information such as the change history of the project
configuration.
2. Drive controller tab:
Select the SC6 series and the device type of the drive controller.
3. Option modules tab:
Safety module: If the drive controller is part of a safety circuit, select the SR6 or SY6 safety module.
4. Device controller tab:
Device controller: Select the device controller that defines the underlying activation signals for the drive controller.
Rx process data, Tx process data: If you control the drive controller using a fieldbus, select the fieldbus-specific receive
and send process data.
If you operate the drive controller in combination with the SY6 safety module, select EtherCAT Rx and EtherCAT Tx for
transmitting the EtherCAT process data.
If you operate the drive controller in combination with the SR6 safety module or without safety technology (SZ6), the
fieldbus connection is optional. If you do not use a fieldbus, project No transmission.