E6582062
5. [Fundamental operation] How to use parameters 5-10
4
5
9
(2) Setting the upper and lower limits of the output frequency
<UL: Upper limit frequency>
<LL: Lower limit frequency>
Function
Set the upper limit frequency to decide the upper limit of the output frequency and the lower limit fre-
quency to decide the lower limit.
Parameter setting
Guideline for the setting
Set <UL: Upper limit frequency> to a value which is ten times or less the values of <vL: Base
frequency 1>.
If the output frequency is exceeding to 10 times of <vL>, the "A-05" alarm will appear, and the value
of the output frequency will be limited to a value which is 10 times the value of <vL: Base frequency
1>.
The same holds for Base frequency 2 - 4. (Refer to [6. 4].)
Title Parameter name Adjustment range Unit
Default
setting
UL Upper limit frequency 0.0 - FH Hz
50.0/60.0
*1
*1 Depending on the setup menu. Refer to [5. 3. 10].
LL Lower limit frequency 0.0 - UL Hz 0.0
0.0HzSTOP
15:08
Min: 0.0 Max: 80.0
X1000 X100 X10 X1
Hz
UL :Upper limit frequency
60.0
Basic parameter Easy mode
Basic parameter Easy mode
0.0HzSTOP
15:08
Min: 0.0 Max: 60.0
X1000 X100 X10 X1
Hz
LL :Lower limit frequency
0.0