E6582062
5. [Fundamental operation] How to use parameters 5-12
4
5
9
5. 2. 4 Setting acceleration/deceleration time
<ACC: Acceleration time 1>
<dEC: Deceleration time 1>
Function
Set a time for acceleration and deceleration.
In <ACC: Acceleration time 1>, set a time before the output frequency of the inverter reaches the
value of <FH: Maximum frequency> from 0.0 Hz.
In <dEC: Deceleration time 1>, set a time before the output frequency of the inverter decreases to
0.0 Hz from the value of <FH: Maximum frequency>.
Unit for a setting time is selected with <F519: Unit of Acc/Dec time>.
Parameter setting
Title Parameter name Adjustment range Unit Default setting
ACC Acceleration time 1 0.0 - 6000 (600.0) s
*1
*1 The default is 10.0/30.0/60.0 (s) depending on the capacity. Refer to [11. 6].
dEC Deceleration time 1 0.0 - 6000 (600.0) s
*1
Title Parameter name Adjustment range
Default
setting
F519 Unit of Acc/Dec time 0: -
1: 0.01s unit (0 after execution)
2: 0.1s unit (0 after execution)
0
0.0HzSTOP
15:09
ACC :Acceleration time 1
Min: 0.0 Max: 6000.0
X1000 X100 X10 X1
s
10.0
Basic parameter Easy mode
Basic parameter Easy mode
0.0HzSTOP
15:10
dEC :Deceleration time 1
Min: 0.0 Max: 6000.0
X1000 X100 X10 X1
s
10.0

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m