EasyManuals Logo

Toshiba TOSVERT VF-AS3 User Manual

Toshiba TOSVERT VF-AS3
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #189 background imageLoading...
Page #189 background image
E6582062
5-23 5. [Fundamental operation] How to use parameters
3
4
5
9
18, 19 : 200% of rated power
20, 21 : 1000 x F749
24, 25, 26, 28, 29, 31, 41, 44, 45, 74, 75, 76, 160, 161, 162
: Maximum value
27, 71 : FH x 60/F856
46, 47 : 65535
48, 49 : 32767
120, 124 : 200°C
When <FMSL: Terminal FM adjustment> and <F670: Terminal AM adjustment> are set "23", signal
value is fixed at half of the above values.
For 4 - 20 mA output
Adjust the values of <F682: Terminal FM inclination polarity> and <F683: Terminal FM bias> for 4 -
20 mA output.
For details, refer to [6. 33. 3].
5. 2. 7 Selecting the display units for current and voltage
<F701: Current, voltage units select>
Memo
The maximum resolution is 1/1024 for both the terminals [FM] and [AM].
To use the terminals [FM] and [AM] for current output, set external load resistance to 600 or
less.
To use the terminals [FM] and [AM] for voltage output, set external load resistance to 1k or
more.
<FM>
<FM>
<F683>
(mA)
20
100%
Internal
calculated value
Analog output current Analog output current
0
0
(mA)
20
4
100%
Internal
calculated value
0
This is when <F682: Terminal FM inclination
polarity> is "1: Positive inclination (upward slope)"
and <F683: Terminal FM bias> is "0". When<F682>
is set to "0: Negative inclination (downward slope)",
the inclination becomes negative.
This is when <F682> is "1" and <F683: Terminal FM
bias> is "20". 20% value (4mA) of the full scale
output current (20 mA in this case) will be the output
current at internal calculated value of 0%.
0.0HzSTOP
15:14
F701 : Current, voltage units select
0: %
1: A(ampere),V(volt)
Easy mode

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals