E6582062
5-69 5. [Fundamental operation] How to use parameters
3
4
5
9
Important
At restart, it takes about 1 second for the inverter to check the motor speed. For this reason, the
startup takes more time than usual.
Use this function when operating a system with one motor connected to one inverter. This
function may not operate properly in a system configuration when multiple motors are
connected to one inverter.
When using this parameter, do not set <F605: Output phase loss detection> to "1", "2", or "4".
For details, refer to [6. 30. 5].
Do not apply it for cranes.
The load may be lowered during waiting time from input of the run command to startup. To
apply the inverter to cranes, therefore, set <F301: Auto-restart> to "0: Disabled". Do not use the
retry function, either.
This function is always enabled at torque control. (independent to <F301> setting)
Memo
When the motor is restarted from retry, this function is operated regardless of the setting of this
parameter.
It is not malfunction that abnormal noise might be heard from the motor during the motor speed
search at the auto-restart.