6-3 6. [Advanced] How to use parameters
3
4
6
9
6. 1. 2 Output a signal when reached to a frequency
command (output the Acc/Dec completed signal)
<F102: Reach signal detection band>
Function
When the output frequency becomes the frequency command ±<F102: Reach signal detection
band>, the Acc/Dec completed signal is output from the output terminal.
Parameter setting
Output terminal parameter setting
Acc/Dec completed signal is the default setting for output terminal [FP].
Title Parameter name Adjustment range Unit Default setting
F102 Reach signal detection
band
0.0-FH Hz 2.5
Title Parameter name Adjustment range Default setting
F130 Terminal FP function 1
0-255
*1
*1 For details on the output terminal functions, refer to [7. 2. 2].
6
0.0HzSTOP
12:43
F102 : Reach signal detect band
Min: 0.0 Max: 80.0
X1000 X100 X10 X1
Hz
2.5
ON
OFF
Output frequency (Hz)
Time (s)
Frequency command value
Frequency command value +
Terminal [FP]
(Acc/Dec completed)
ON
OFF
Terminal [F]
(Fwd run)
0
Frequency command value -
<F102>
<F102>

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals