E6582062
6. [Advanced] How to use parameters 6-106
4
4
6
9
Setting example
Select destination of tension control torque bias input and load sharing gain input.
When setting with input of 0 to 10 Vdc to terminal [RR]
Set <F423: Tension control torque bias input> = "1" or <F424: Load sharing gain input> = "1".
When setting with input of -10 to +10 Vdc to terminal [RX]
Set <F423: Tension control torque bias input> = "2" or <F424: Load sharing gain input> = "2".
When setting with input of 4 to 20 mAdc to terminal [II]
Set <F423: Tension control torque bias input> = "3" or <F424: Load sharing gain input> = "3".
Reference
How to operate the operation panel -> Refer to [3. 1. 1].
How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Procedure to change parameter setting -> Refer to [4. 2. 3]
Details on operation by external signals -> Refer to [Chapter 7].