EasyManua.ls Logo

Toshiba TOSVERT VF-AS3 - Page 373

Toshiba TOSVERT VF-AS3
622 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6582062
6-131 6. [Advanced] How to use parameters
3
4
6
9
1: Enabled
The inverter trips when the power running torque value is <F616> or more, or the regen torque value
is <F617> or more, is detected over the period of time specified by <F618> or longer. Overtorque
(OT) alarm can also be output from the output terminal. (Failure signal FL enabled)
Setting example
Assign "28: Overtorque (OT) alarm" to the unused output terminal.
In the case of <F615: Overtorque trip> = "0: Disabled", the alarm functions as follows.
When <F615: Overtorque trip> = "1: Enabled", the inverter trips if overtorque is detected for the
period of time specified by <F618: Overtorque detection time>.
After that, overtorque (OT) alarm remains ON.
Reference
How to operate the operation panel -> Refer to [3. 1. 1].
How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Procedure to change parameter setting -> Refer to [4. 2. 3]
Details on operation by external signals -> Refer to [Chapter 7].
Torque (%)
Overtorque
signal output
ON
OFF
Below <F618>
OFF
Time (s)
<F616>
<F618>
<F619><F616>

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Related product manuals