E6582062
6. [Advanced] How to use parameters 6-176
4
4
6
9
6. 34. 10 Setting torque command value in panel run
<F725: Panel torque command>
Function
This parameter is used to set a torque command value when torque control is performed in panel
run.
Parameter setting
Guideline for the setting
<F725: Panel torque command> is enabled only when <F420: Torque command select> is "12" and
acts as command value(%).
For details, refer to torque control (E6582106).
Title Parameter name Adjustment range Unit Default setting
F725 Panel torque command -250 to +250 % 0
Reference
How to operate the operation panel -> Refer to [3. 1. 1].
How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Procedure to change parameter setting -> Refer to [4. 2. 3]
Details on operation by external signals -> Refer to [Chapter 7].