E6582062
6. [Advanced] How to use parameters 6-186
4
4
6
9
F814 Communication point 2
frequency
0.0-FH Hz
50.0/60.0
*4
F820
RS485 (2) baud rate
*1
0: 9600 bps
1: 19200 bps
2: 38400 bps
1
F821
RS485 (2) parity
*1
0: Disabled
1: Even parity
2: Odd parity
1
F823 RS485 (2) time-out time
*2
0.0: Disabled
0.1 - 100.0 s
0.0
F824 RS485 (2) time-out
operation
*2
1: Continue running
2, 3: -
4: Trip
5: -
6: Trip after Deceleration stop
0
F825 RS485 (2) transmission
wait time
0.00 - 2.00 s 0.00
F826 RS485 (2) inverter to
inverter communication
*1
0: Follower (0Hz command when Leader
fails)
1: Follower (continue running when Leader
fails)
2: Follower (emergency off when Leader
fails)
3: Leader (transmit frequency command)
4: Leader (transmit output frequency signal)
5: Leader (transmit torque command)
6: Leader (transmit output torque command)
0
F827 RS485 (2) protocol 0: TOSHIBA
1: MODBUS
0
F828 RS485 (2) time-out
detection
0: Always
1: Run command and frequency command
by communication are enabled.
2: During run by communication
1
F829 RS485 (2) wiring type 0: 2-wire
1: 4-wire
0
F830 MODBUS continuous
address
0: Disabled
1: Enabled
0
F856 Motor pole number for
communication
1: 2 pole
2: 4 pole
3: 6 pole
4: 8 pole
5: 10 pole
6: 12 pole
7: 14 pole
8: 16 pole
2
F870 Block write data 1 0: Disabled
1: Communication command 1
2: Communication command 2
3: Frequency command
4: TB output
5: Analog output
6: Speed command by communication
0
F871 Block write data 2 0
Title Parameter name Adjustment range Unit Default setting