E6582062
6-187 6. [Advanced] How to use parameters
3
4
6
9
Communication option
Refer to [10. 3. 5] and [10. 3. 6] for options connected to RS485 communication connectors.
To use these options, set <F805: RS485 (1) transmission wait time > to "0.00".
F875 Block read data 1 0: Disabled
1: Status information
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal monitor
8: Output terminal monitor
9: Terminal RR monitor
10: Terminal RX monitor
11: Terminal II monitor
12: Input voltage (DC detection)
13: Speed feedback frequency
14: Torque
15: My function output monitor 1
16: My function output monitor 2
17: My function output monitor 3
18: My function output monitor 4
19: Free memorandum
20: Motor speed
21: Input power
22: Output power
23: Trip information
0
F876 Block read data 2 0
F877 Block read data 3 0
F878 Block read data 4 0
F879 Block read data 5 0
F899 Communication option
reset
0: -
1: Reset option and inverter
0
*1 Valid after the setting is changed and the power is turned off and on again.
*2 The setting contents are as follows.
- Disabled: The inverter does not trip even if a communication error occurs.
- Trip: The inverter trips when communication time-over occurs, and "Err5" is displayed.
- Alarm: When communication time-over occurs, an alarm can be output from the output
terminal. Assign the output terminal function "78" (RS485 communication time-out) (79 is
inversion output) to the output terminal.
*3 When using RS485 communication, set <F809>="0".
*4 Depending on the setup menu. Refer to [11. 10].
Reference
How to operate the operation panel -> Refer to [3. 1. 1].
How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Procedure to change parameter setting -> Refer to [4. 2. 3]
Title Parameter name Adjustment range Unit Default setting