EasyManuals Logo

Toshiba TOSVERT VF-S11 User Manual

Toshiba TOSVERT VF-S11
269 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #237 background imageLoading...
Page #237 background image
E6581158
K-11
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0619 Over-torque
detection level
hysteresis
% 1/1 0-100 10 6.19.9
H
0621 Cumulative
operation time
alarm setting
100
Time
0.1/0.1
(=10 hours)
0.0-999.9 610 6.19.10
H
0626 Over-voltage stall
protection level
%
1/1 100-150 *1 6.13.5
H
0627 Undervoltage
trip/alarm
selection
- - 0: Alarm only
(detection level below 60%)
1: Tripping
(detection level below 60%)
2: Alarm only
(detection level below 50%,
DC reactor necessary)
0 6.19.12
H
0633 Trip at VIA low
level input mode
1/1 0: Disabled, 1-100 0 6.19.13
H
0634 Annual average
ambient
temperature
(calculation for life
alarms)
- - 1: -10 to +10cC
2: 11-20cC
3: 21-30cC
4: 31-40cC
5: 41-50cC
6: 51-60cC
3 6.19.14
Output parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0669 Logic output/pulse
train output
selection (OUT-
NO)
- - 0: Logic output
1: Pulse train output
0 6.20.1
H
0676 Pulse train output
function selection
(OUT-NO)
--
0: Output frequency
1: Output current
2: Set frequency
3: DC voltage
4: Output voltage command value
5: Input power
6: Output power
7: Torque
8: Torque current
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (braking reactor) cumulative
load factor
12: Frequency setting value (after
PID)
13: VIA/II Input value
14: VIB Input value
15: Fixed output 1 (Output current:
100%)
16: Fixed output 2 (Output current:
50%)
17: Fixed output 3
(Other than the output current:
100%)
0 6.20.1
H
0677 Maximum nembers
of pulse train
pps 1/1 500-1600 800 6.20.1
H
0691 Inclination
characteristic of
analog output
- - 0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
1 6.20.2
H
0692 Meter bias % 1/1 0100 0 6.20.2
*1 : Default values vary depending on the capacity. See the table of K-14.

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)

Related product manuals