UNIT SETUP
Confi guring Controller Settings
FMS-1650
TRIATEK reserves the right to change product specifications without notice.
- 13 -
option invokes the Alarm Buzzer Settings configuration screen shown
in Figure 19. At this configuration screen, each analog input may be
individually enabled for audible alerts. Clicking the Next button invokes
the next Alarm Buzzer Settings configuration screen shown in Figure
20.
The alarm buzzer may be selected for one of two modes of operation:
Audible Mode or Silent Mode. If audible mode is selected, the user is
prompted to enter the desired delay in seconds or minutes. If silent
mode is selected, then the alarm buzzer will not sound whenever
the unit enters alarm status. If audible mode is selected, clicking the
Next button invokes the next Alarm Buzzer Settings configuration
screen shown in Figure 21, which allows the user to specify an Alarm
Quiet Period. This feature allows the audible alerts to be suppressed
between the specified hours every day, thereby eliminating the
potential for nuisance alarms.
In the example shown in Figure 21, the alarm buzzer will be muted
between the hours of 9:00 pm and 5:00 am every day. Hospitals may
take advantage of this feature to minimize nuisance alarms during non-
visiting hours in patient rooms.
Figure 19. Each
analog input may be
independently enabled
to trigger the alarm
buzzer.
Figure 20. The
alarm buzzer can be
configured for audible
or silent mode. In
audible mode, a buzzer
delay may be specified
in seconds or minutes.
Figure 21. An Alarm
Quiet Period may be
specified, during which
the alarm buzzer is
muted between the
starting hour and
ending hour.