Watlow F4T 233 Chapter 6 Appendix
Parameter Class
and Name
Range Default
Data Type and
Attributes
Modbus Registers
Minimum Manual
Power
-100 To 100% -100.0
"IEEE Float
Access=RW"
"Cascade Loop 1: 4038
Cascade Loop n:
4038+((n-1)* 200)"
Maximum Manual
Power
-100 To 100% 100.0
"IEEE Float
Access=RW"
"Cascade Loop 1: 4040
Cascade Loop n:
4040+((n-1)* 200)"
Set Point
[Min Set Point] To [Max
Set Point]
75.0°F or units,
23.9°C
"IEEE Float
Access=RW"
"Cascade Loop 1: 4042
Cascade Loop n:
4042+((n-1)* 200)"
Manual Power
[Min Manual Power] To
[Max Manual Power]
0.0
"IEEE Float
Access=RW"
"Cascade Loop 1: 4044
Cascade Loop n:
4044+((n-1)* 200)"
Idle Set Point
[Min Set Point] To [Max
Set Point]
75.0°F or units,
23.9°C
"IEEE Float
Access=RW"
"Cascade Loop 1: 4046
Cascade Loop n:
4046+((n-1)* 200)"
Auto-to-Manual Power
"Off (62)
Bumpless Transfer (14)
Fixed Power (33)
User (100)"
User (100)
"unsigned 16-bit
Access = RW"
"Cascade Loop 1: 4048
Cascade Loop n:
4048+((n-1)* 200)"
Input Error Power
"Off (62)
Bumpless Transfer (14)
Fixed Power (33)
User (100)"
User (100)
"unsigned 16-bit
Access = RW"
"Cascade Loop 1: 4050
Cascade Loop n:
4050+((n-1)* 200)"
Fixed Power
[Min Manual Power] To
[Max Manual Power]
0.0
"IEEE Float
Access=RW"
"Cascade Loop 1: 4052
Cascade Loop n:
4052+((n-1)* 200)"
Ramp Action
"Off (62)
Startup (88)
Set Point (85)
Both (13)"
Off (62)
"unsigned 16-bit
Access = RW"
"Cascade Loop 1: 4054
Cascade Loop n:
4054+((n-1)* 200)"
Ramp Scale
"Hours (39)
Minutes (57)"
Minutes (57)
"unsigned 16-bit
Access = RW"
"Cascade Loop 1: 4056
Cascade Loop n:
4056+((n-1)* 200)"
Ramp Rate
0 to 99,999°F or units, 0
to 55,555°C
1.0
"IEEE Float
Access=RW"
"Cascade Loop 1: 4058
Cascade Loop n:
4058+((n-1)* 200)"
Remote Set Point
"No (59)
Yes (106)"
No (59)
"unsigned 16-bit
Access = RW"
"Cascade Loop 1: 4060
Cascade Loop n:
4060+((n-1)* 200)"
Remote Set Point Type
"Auto (10)
Manual (54)"
Auto (10)
"unsigned 16-bit
Access = RW"
"Cascade Loop 1: 4062
Cascade Loop n:
4062+((n-1)* 200)"
Cool Output Curve
"Off (62)
Non-linear curve 1 (214)
Non-linear curve 2
(215)"
Off (62)
"unsigned 16-bit
Access = RW"
"Cascade Loop 1: 4064
Cascade Loop n:
4064+((n-1)* 200)"
Heat Proportional
Band Inner Loop 1
0.001 to 99,999.000°F
or units, 0.001 to
55,555.000°C
25.0°F or units,
13.0°C
"IEEE Float
Access=RW"
"Cascade Loop 1: 4066
Cascade Loop n:
4066+((n-1)* 200)"
Cool Proportional
Band Inner Loop 1
0.001 to 99,999.000°F
or units, 0.001 to
55,555.000°C
25.0°F or units,
13.0°C
"IEEE Float
Access=RW"
"Cascade Loop 1: 4068
Cascade Loop n:
4068+((n-1)* 200)"
Integral Inner Loop 1
0 To 99999 seconds per
repeat
180.0
"IEEE Float
Access=RW"
"Cascade Loop 1: 4070
Cascade Loop n:
4070+((n-1)* 200)"

Table of Contents