Watlow F4T 83 Chapter 5 Function Reference
3. Error Status
A signal's error status indicates whether or not the value can be relied on. A signal with
no errors (error status is none), is displayed as a black line in Composer. When some-
thing is wrong such that a function block cannot determine an appropriate value to
transmit, the signal is displayed as a yellow line in Composer. You can determine the
specific error status by mousing over the signal in the diagram. The table below lists
the possible errors that could be presented to the user. Any error status other than
none is considered an error.
Error Status Description
None No error is detected.
Open A sensor is broken or disconnected.
Shorted A sensor has failed or is shorted.
Measurement Error A measurement error has occurred.
Bad Calibration The controller has not been calibrated.
Ambient Error
The ambient temperature is outside of the controller's operating
range.
RTD Error An RTD sensor error has occurred.
Fail A measurement failure has occurred.
Not Sourced
The source FB is missing a required signal at one of its receiv-
ers.
Stale Data Data sourced from another controller has become unavailable.
Math Error A calculation has no defined result (such as divide by zero).
This chapter describes in detail each of the available functions as well as their associated pa-
rameters.
Note:
The addresses and other information required to read or set FB parameter values via a
field bus protocol is located in the "Communications" section of the Appendix to this Us-
er's Guide.
Alarm
Use an alarm to monitor an analog signal and set an output when that signal goes above or
below the user-set alarm conditions. This block is found in the Function Block Diagram edi-
tor’s Library when working with a controller that offers the Alarm block. The number of these
blocks available is shown within the parenthesis.
Use the Type parameter to set the blocks behavior. These options for Type are described in
detail in the following sections:
Off: no alarms occur. The blocks output is off.
Process Alarm: monitors an analog signal for specified alarm conditions.
Deviation Alarm: monitors an analog signal for alarm conditions relative to another signal.

Table of Contents

Other manuals for Watlow F4T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watlow F4T and is the answer not in the manual?

Watlow F4T Specifications

General IconGeneral
InputsThermocouple, RTD, mA, V
OutputsRelay, SSR, mA, V
CommunicationEthernet, Modbus RTU
Data LoggingYes
CertificationsCE, UL, cUL, RoHS
Control ModesPID, On/Off
Power Supply100 to 240 VAC
Operating Temperature0 to 50°C
Enclosure RatingIP65
Display4.3 in. (109 mm) color touch panel LCD
Control LoopsUp to 4

Related product manuals