7
OUTPUT FILTERS
Table 7.1: Output filters for MVW01 inverters
Motor cables
length
Inverter model:
Nominal current/ Size
Output dv/dt Filter Components
< 100m
All models
It is not necessary
-
100m - 200m
4160V / A0
Output reactor with 2 %
voltage drop
Reactor according to WEG specification
4160V / A
3300V / A0
3300V / A
2300V / A
2300V / B
4160V / C D E
It is not necessary
-
3300V / C D E
200m - 500m
4160V / A
RLC 02 dV/dt filter
Reactor according to WEG specification
3300V / A
2300V / A
2300V / B
4160V / C
3300V / C
4160V / D
3300V / D
4160V / E
3300V / E
> 500m
All models
Sinusoidal filter Under consultation to WEG
(*) Output filters for MVW01 inverters 6000-6900V on request.
MVW01 | 7-2