10
INSTALLATION, CONNECTION AND ENERGIZATION
Figure 10.3: Compact power arm with package
10.1.6 Positioning/Mounting
The MVW01 panel must be placed on a flat leveled surface, thus avoiding mechanical instability, door misalignment, among other problems.
WARNING!
Some MVW01 models are sectioned for transport purposes. The sectioned parts must be properly coupled during start-up.
The permanent operation position must allow heat radiation from all the surfaces and the necessary ventilation for its operation. The area in
front of the panel must remain unobstructed, so that a total opening of the doors be possible, as well as the insertion and extraction of the
arms and/or the power and control cables.
The Table 3.1 on page 3-3 shows the panel dimensions.
WARNING!
Make sure there is access for the electric connections: Input cables at the rectifier column and the output for the motor, main
circuit breaker commands and status, transformer and motor protections, analog and digital inputs and outputs.
It is necessary to provide space behind the panel for rear access to internal components during the installation of the product.
MVW01 | 10-5