SSW-06 - QUICK PARAMETER REFERENCE
18
Parameter Description Adjustable Range Factory Unit User´s Pag e
Setting Setting
P613
(1)
Immediate Overcurrent Time 0=Inactive 0=Inactive s 126
1 to 99
P614
(1)
Current Imbalance between Phases 0 to 30 15 % 126
(% In of the Motor)
P615
(1)
Current Imbalance between 0=Inactive 1 s 126
Phases Time 1 to 99
P616
(1)
Undercurrent before 0=Inactive 1=Active - 127
By-pass Closing 1=Active
P617
(1)
LockedRotoratthe 0=Inactive 1=Active - 127
Start End 1=Active
P618
(1)
Ground Fault 10 to 30 20 % 127
P619
(1)
Ground Fault Time 0 to 10.0 0=Inactive s 127
Phase Sequence
P620
(1)
RST Phase Sequence 0=Inactive 0=Inactive - 127
1=Active
By-pass Contactor Closed Detection
P621
(1)
By-pass Contactor Closed 0=Inactive 1=Active 127
1=Active
By-pass Contactor Closed Detection
P622
(1)
Short Circuit in the SSW Power 0=Inactive 0=Inactive 127
1=Active
Interval between Starts
P630 Interval of Time after Stop 2 to 999 2 s 127
Short Circuit Detection in the Power of the SSW
P640
(1)
Motor Protection Thermal Class 0=Inactive 5=25 6=30 - 129
1=5 6=30
2=10 7=35
3=15 8=40
4=20 9=45
P641
(1)
Auto-Reset of the Thermal Memory 0=Inactive 0=Inactive s 132
1 to 600
P642 Motor Thermal Protection Alarm 0 to 250 230 % 133
P643 Motor Thermal Protection Alarm Reset 0 to 250 210 % 133
Torque Protections
P650
(1)
Immediate Undertorque 0 to 99 30 % 133
(% Tn of the Motor)
P651
(1)
Immediate Undertorque Time 0 to 99 0=Inactive s 133
P652
(1)
Immediate Overtorque 0 to 99 30 % 133
(% Tn of the Motor)
P653
(1)
Immediate Overtorque Time 0 to 99 0=Inactive s 133
Power Protections
P660
(1)
Immediate Underpower 0 to 99 30 % 134
(% kWn of the Motor)
P661
(1)
Immediate Underpower Time 0 to 99 0=Inactive s 134
P662
(1)
Immediate Overpower 0 to 99 30 % 134
(% kWn of the Motor)
P663
(1)
Immediate Overpower Time 0 to 99 0=Inactive s 134
Motor Thermal Protection (Optional PT100)
P670 PT100 Inputs Card Enable 0=No 0=No - 134
1=Yes
P671 Motor Overtemperature Ch 1 0=Inactive 0=Inactive - 135
1=Error E33