19
SSW-06 - QUICK PARAMETER REFERENCE
Parameter Description Adjustable Range Factory Unit User´s Pag e
Setting Setting
2=Alarm A33
3=E33 and A33
P672 Motor Overtemperature Error 0 to 250 139 ºC 136
Actuation LevelCh1
P673 Motor Overtemperature Alarm 0 to 250 124 ºC 136
ActuationLevelCh1
P674 Motor Overtemperature Alarm 0 to 250 108 ºC 137
ResetLevelCh1
P675 Motor Overtemperature Ch 2 0=Inactive 0=Inactive - 137
1=Error E34
2=Alarm A34
3=E34 and A34
P676 Motor Overtemperature Error 0 to 250 139 ºC 136
Actuation LevelCh2
P677 Motor Overtemperature Alarm 0 to 250 124 ºC 136
ActuationLevelCh2
P678 Motor Overtemperature Alarm 0 to 250 108 ºC 137
ResetLevelCh2
P679 Motor Overtemperature Ch 3 0=Inactive 0=Inactive - 137
1=Error E35
2=Alarm A35
3=E35 and A35
P680 Motor Overtemperature Error 0 to 250 139 ºC 136
Actuation LevelCh3
P681 Motor Overtemperature Alarm 0 to 250 124 ºC 136
ActuationLevelCh3
P682 Motor Overtemperature Alarm 0 to 250 108 ºC 137
ResetLevelCh3
P683 Motor Overtemperature Ch 4 0=Inactive 0=Inactive - 137
1=Error E36
2=Alarm A36
3=E36 and A36
P684 Motor Overtemperature Error 0 to 250 139 ºC 136
Actuation LevelCh4
P685 Motor Overtemperature Alarm 0 to 250 124 ºC 136
ActuationLevelCh4
P686 Motor Overtemperature Alarm 0 to 250 108 ºC 137
ResetLevelCh4
P687 Motor Overtemperature Ch 5 0=Inactive 0=Inactive - 137
1=Error E37
2=Alarm A37
3=E37 and A37
P688 Motor Overtemperature Error 0 to 250 139 ºC 136
Actuation LevelCh5
P689 Motor Overtemperature Alarm 0 to 250 124 ºC 136
ActuationLevelCh5
P690 Motor Overtemperature Alarm 0 to 250 108 ºC 137
ResetLevelCh5
P691 PT100 Sensors Fault (Ch1 to Ch5) 0=Inactive 0=Inactive - 137
1=E43 to E52
2=A43 to A52