1125100 WPC 1000 User Manual
5-8 Troubleshooting
Problem: The Top Stop button on the Operator Station was depressed or the Top-stop circuit
was open after initiation of the stroke.
Remedy: Check other equipment (e.g. DiPro 1500, AutoSet, etc.) wired into the Top-stop
string. Correct the problem. Reset the other equipment first; then reset WPC 1000
and restart the press.
Problem: Cross-checked inputs 3A & 3B were in different states (i.e., open or closed) for
longer than 100 mS.
Remedy: Diagnose and correct the condition that the inputs are monitoring (see Table 5-2,
page 5-12).
Problem: You are attempting to run the main motor in reverse without selecting Two-hand
Inch mode.
Remedy: Switch to Two-hand Inch mode, then run the motor in reverse.
Problem: The N/O inputs from the Run/Inch palm buttons on the Operator Station do not
turn off (i.e., open) when they should.
Remedy: Check to make sure that the palm buttons are the correct switch type. Check and
correct the palm switch wiring. If the error persists, call Wintriss Tech. Support.
Problem: The operating mode was changed while the press was running.
Remedy: Make your operating mode selection before running the press.
F16
F17
F20
F21
F22