1125100 WPC 1000 User Manual
2-68 Installation
6. Power up the press and press control, make sure the press is in Inch mode, and push both
Run/Inch buttons. Observe what happens.
If the ram does not move and the display shows F79 or one of the DSV faults, the DSV
is operating properly. Go to the next step.
If the ram moves and/or the display shows a fault other than F79 or one of the DSV
faults, check the wiring of the DSV and correct any problems, then repeat step 6. If the
ram still moves and/or the display still shows a fault other than F79 or one of the DSV
faults, power down the press immediately and call Wintriss Tech. Support.
7. Power down the press and press control, and replace the fuse you removed in step 5.
8. Power up the press and press control, make sure the press is still in Inch mode, and push
both Run/Inch buttons briefly. The ram should move.
If the ram moves, go to the next section.
If the ram does not move, check the wiring of the DSV and correct any problems.
Power up the press and press control. Push the Run/Inch buttons again. If the ram still
does not move, call Wintriss Tech. Support.
Checking for Error Messages
To check for error messages, do the following:
1. Run the press in Inch for a few strokes.
If the press runs normally, go to the next section.
If a fault appears on the display, look up the fault code in Chapter 5, and follow the
remedy provided. Once the problem is corrected, press the Reset/Select button, and run
the press again in Inch for a few strokes, checking for error codes. If you need
assistance, call Wintriss Tech. Support.
Checking the Emergency-stop Circuit
To check the Emergency-stop circuit, do the following:
1. Run the press in Inch mode. While the ram is moving, have someone push the Emergency
Stop button on the Operator Station. The press should Emergency-stop immediately.
If the press Emergency-stops, go to the next section.
If the press does not Emergency-stop, there is a problem in your E-stop circuit.
Recheck wiring and correct any problems, then repeat this test. If the press still does not
Emergency-stop, call Wintriss Tech. Support. Do not continue with this checkout
procedure until the press E-stops correctly.
Installation Verification Complete
The WPC 1000 Installation Verification procedure is complete. Clear any error message by
pressing the Reset/Select button.