166 Parameters
16.11 User IO sel lo When parameter 16.09 User set sel is set to IO mode,
selects the user parameter set together with parameter
16.12 User IO sel hi. The status of the source defined by this
parameter and parameter 16.12 select the user parameter
set as follows:
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
16.12 User IO sel hi See parameter 16.11 User IO sel lo.
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
16.14 Reset ChgParLog Resets the log of latest parameter changes.
Done Reset not requested (normal operation). 0
Reset Reset log of latest parameter changes. The value reverts
automatically to Done.
1
16.16 Menu set active Shows which parameter list is active. Parameter lists
determine which parameters are displayed.
See also parameter 16.21 Menu selection.
None No specific parameter list is active. 0
Single short A selective list of parameters relevant to the single pump
(factory default) application macro is displayed.
1
Single long A more comprehensive list of parameters relevant to the
single pump (factory default) application macro is displayed.
2
Trad short A selective list of parameters relevant to the traditional pump
control application macro is displayed.
3
Trad long A more comprehensive list of parameters relevant to the
traditional pump control application macro is displayed.
4
Ext short A selective list of parameters relevant to the external control
application macro is displayed.
5
Ext long A more comprehensive list of parameters relevant to the
external control application macro is displayed.
6
H/A short A selective list of parameters relevant to the Hand/Auto
control application macro is displayed.
7
H/A long A more comprehensive list of parameters relevant to the
Hand/Auto control application macro is displayed.
8
Level short A selective list of parameters relevant to the Level control
application macro (single-pump) is displayed.
9
Level long A more comprehensive list of parameters relevant to the
Level control application macro (single-pump) is displayed.
10
No. Name/Value Description FbEq
Status of source
defined by par.
16.11
Status of source
defined by par.
16.12
User parameter
set selected
FALSE FALSE Set 1
TRUE FALSE Set 2
FALSE TRUE Set 3
TRUE TRUE Set 4