Parameters 217
Sunday Time period 1 ends on Sunday. 7
36.19 Boost signal Boosting can be used to extend the timer enable signal for
the time defined by parameter 36.20 Boost time. The boost
time starts when the boost signal changes state from 1 to 0.
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
36.20 Boost time Boost time. See parameter 36.19 Boost signal.
00:00:00 …
24:00:00
Boost time. 1 = 1 s
(24:00:00 =
86400)
36.21 Timed func1 Selects which time periods (1…4) are used with timed
function 1. Also determines whether boost is used with timed
function 1.
The parameter is a 16-bit word with each bit corresponding
to a function. Whenever a bit is set to 1, the corresponding
function is in use.
The bits of the binary number correspond to the following
functions:
36.22 Timed func2 Selects which time periods (1…4) are used with timed
function 2. Also determines whether boost is used with timed
function 2.
The parameter is a 16-bit word with each bit corresponding
to a function. Whenever a bit is set to 1, the corresponding
function is in use.
The bits of the binary number correspond to the following
functions:
No. Name/Value Description FbEq
Bit Function
0 Timer1 ena (Time period 1 enable)
1 Timer2 ena (Time period 2 enable)
2 Timer3 ena (Time period 3 enable)
3 Timer4 ena (Time period 4 enable)
4 Boost ena (Boost enable)
Bit Function
0 Timer1 ena (Time period 1 enable)
1 Timer2 ena (Time period 2 enable)
2 Timer3 ena (Time period 3 enable)
3 Timer4 ena (Time period 4 enable)
4 Boost ena (Boost enable)