Parameters 251
76.04 Pump prior sel Defines a source that chooses a start priority for the drive.
Two preset priorities are available: either can be selected
permanently, or a digital signal source used to switch
between the two presets.
Please note that the Autochange feature will attempt to
equalize the duty between drives with the same priority
rather than between drives with different priorities.
With a digital source,
0 = priority defined by 76.05 Prior choice 1
1 = priority defined by 76.06 Prior choice 2.
Choice 1 Start priority defined by parameter 76.05 Prior choice 1.0
Choice 2 Start priority defined by parameter 76.06 Prior choice 2.1
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
76.05 Prior choice 1 Priority preset 1. See parameter 76.04 Pump prior sel.
1…4 Priority preset 1. 1 = 1
76.06 Prior choice 2 Priority preset 2. See parameter 76.04 Pump prior sel.
1…4 Priority preset 2. 1 = 1
76.07 Mstr loss action If the drive is a follower, cannot find a master on the drive-to-
drive link, and is not itself allowed to be master, it will wait for
the delay specified by parameter 76.08 Mstr loss delay, then
proceed as defined by this parameter. The drive will also
generate an alarm.
Const speed The drive continues running and adopts the speed defined
by parameter 26.08 Const speed3.
0
Last speed The drive continues running at the last valid reference
received from the master.
1
76.08 Mstr loss delay Delay for a master loss situation. See parameter 76.07 Mstr
loss action.
0…3600 s Delay for master loss. 1 = 1 s
No. Name/Value Description FbEq