Parameters 275
81.11 AI out hi level Pressure limit for primary outlet pressure supervision. See
parameter 81.09 Outlet prot ctrl.
0.00 … 32767.00
bar
Pressure limit. 100 = 1 bar
81.12 Very high ctrl Enables the secondary supervision of pump outlet pressure
and selects the action taken when very high outlet pressure
is detected. The selected action is taken only after the
measured pressure has remained above the pressure limit
(81.13 AI out very high) for longer than the value of
parameter 81.15 Outlet ctr dly. See the diagram at
parameter 81.09 Outlet prot ctrl.
Note: With a pressure switch, this parameter has no effect.
Not sel Secondary outlet pressure supervision not used. 0
Fault Detection of very high outlet pressure trips the drive. 1
Stop Detection of very high outlet pressure stops the drive. The
drive will restart if the pressure falls below the limit.
2
81.13 AI out very high Pressure limit for secondary outlet pressure supervision.
See parameter 81.12 Very high ctrl.
0.00 … 32767.00
bar
Pressure limit. 100 = 1 bar
81.14 DI status outlet Selects the digital input for connection of a pressure switch
at the pump outlet. The “normal” state is 1. If the selected
input switches to 0, the action defined by parameter 81.09
Outlet prot ctrl is taken after the delay set by parameter
81.15 Outlet ctr dly expires.
Not used No pressure switch connected. 1074070017
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
81.15 Outlet ctr dly Delay for primary and secondary supervision of pump outlet
pressure. See parameter 81.09 Outlet prot ctrl.
0…600 s Delay. 1 = 1 s
81.16 Outlet force ref Pump speed reference for parameter 81.09 Outlet prot ctrl,
selection Protect.
0.0 … 32767.0 rpm Speed reference. 10 = 1 rpm
81.17 Protect dec time PID controller ramp-down time for parameter
81.09 Outlet
prot ctrl, selection Protect.
0…18000 s PID controller ramp-down time for outlet pressure
supervision.
1 = 1 s
81.18 Flow source sel Selects an source for flow measurement for
minimum/maximum flow protection. See parameters 81.19
Flow max prot and 81.21 Flow min prot.
AI1 scaled 02.05 AI1 scaled (see page 113). 1073742341
AI2 scaled 02.07 AI2 scaled (see page 113). 1073742343
No. Name/Value Description FbEq