Additional parameter data 303
38.05 U/f curve freq2 REAL 16 1…500 % 30%
38.06 U/f curve freq3 REAL 16 1…500 % 50%
38.07 U/f curve freq4 REAL 16 1…500 % 70%
38.08 U/f curve freq5 REAL 16 1…500 % 90%
38.09 U/f curve volt1 REAL 16 0…200 % 20%
38.10 U/f curve volt2 REAL 16 0…200 % 40%
38.11 U/f curve volt3 REAL 16 0…200 % 60%
38.12 U/f curve volt4 REAL 16 0…200 % 80%
38.13 U/f curve volt5 REAL 16 0…200 % 100%
38.16 Flux ref pointer Val pointer 32 - - P.38.01
40 Motor control
40.01 Motor noise enum 16 0…2 - Cyclic
40.03 Slip gain REAL24 32 0…200 % 100%
40.04 Voltage reserve REAL24 32 -4…50 % -2%
40.07 IR-compensation REAL24 32 0…50 % 0.00%
40.10 Flux braking enum 16 0…2 - Disabled
44 Maintenance
44.01 Ontime1 func Pb 16 0b00…0b11 - 0b01
44.02 Ontime1 src Bit pointer 32 - - Running
44.03 Ontime1 limit UINT32 32 0…2147483647 s 36000000 s
44.04 Ontime1 alm sel enum 16 0…5 - Mot bearing
44.05 Ontime2 func Pb 16 0b00…0b11 - 0b01
44.06 Ontime2 src Bit pointer 32 - - Charged
44.07 Ontime2 limit UINT32 32 0…2147483647 s 15768000 s
44.08 Ontime2 alm sel enum 16 0…5 - Device clean
44.09 Edge count1 func Pb 16 0b00…0b11 - 0b01
44.10 Edge count1 src Bit pointer 32 - - Charged
44.11 Edge count1 lim UINT32 32 0…2147483647 - 5000
44.12 Edge count1 div UINT32 32 0…2147483647 - 1
44.13 Edg cnt1 alm sel enum 16 0…5 - Dc-charge
44.14 Edge count2 func Pb 16 0b00…0b11 - 0b01
44.15 Edge count2 src Bit pointer 32 - - RO1
44.16 Edge count2 lim UINT32 32 0…2147483647 - 10000
44.17 Edge count2 div UINT32 32 0…2147483647 - 1
44.18 Edg cnt2 alm sel enum 16 0…5 - Output relay
44.19 Val count1 func Pb 16 0b00…0b11 - 0b01
44.20 Val count1 src Val pointer 32 - - Speed rpm
44.21 Val count1 lim UINT32 32 0…2147483647 - 13140000
44.22 Val count1 div UINT32 32 0…2147483647 - 6000
44.23 Val cnt1 alm sel enum 16 0…1 - Mot bearing