Parameters 223
44.09 Edge count1 func Configures rising edge counter 1. This counter is
incremented every time the signal selected by parameter
44.10 Edge count1 src switches on (unless a divisor value is
applied – see parameter 44.12 Edge count1 div). After the
limit set by parameter 44.11 Edge count1 lim is reached, an
alarm specified by parameter 44.13 Edg cnt1 alm sel is
given, and the counter reset.
The current value of the counter is readable from parameter
04.11 Counter edge1. Bit 2 of 06.15 Counter status indicates
that the count has exceeded the limit.
44.10 Edge count1 src Selects the signal to be monitored by rising edge counter 1.
See parameter 44.09 Edge count1 func.
RO1 Relay output RO1 (as indicated by 02.02 RO status, bit 0). 1073742338
Running Bit 3 of 06.01 Status word1 (see page 126). 1073939969
Charged Bit 9 of 06.02 Status word2 (see page 127). 1074333186
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
44.11 Edge count1 lim Sets the alarm limit for rising edge counter 1. See parameter
44.09 Edge count1 func.
0 … 2147483647 Alarm limit for rising edge counter 1. 1 = 1
44.12 Edge count1 div Divisor for rising edge counter 1. Determines how many
rising edges increment the counter by 1.
1 … 2147483647 Divisor for rising edge counter 1. 1 = 1
44.13 Edg cnt1 alm sel Selects the alarm for rising edge counter 1. See parameter
44.09 Edge count1 func.
Edge count1 Pre-selectable alarm for rising edge counter 1. 0
Main cntactr Pre-selectable alarm for rising edge counter 1. 1
Output relay Pre-selectable alarm for rising edge counter 1. 2
Motor starts Pre-selectable alarm for rising edge counter 1. 3
Power ups Pre-selectable alarm for rising edge counter 1. 4
Dc-charge Pre-selectable alarm for rising edge counter 1. 5
No. Name/Value Description FbEq
Bit Function
0
Counter mode
0 = Loop: If alarm is enabled by bit 1, the alarm stays active only for 10 seconds.
1 = Saturate: If alarm is enabled by bit 1, the alarm stays active until reset.
1
Alarm ena (Alarm enable)
0 = Disable: No alarm is given when limit is reached.
1 = Enable: Alarm is given when limit is reached.