318 Fault tracing
2055 DEVICE CLEAN
(0x5080)
Maintenance counter alarm. See parameter group 44 Maintenance.
Note: Any maintenance counter alarm
sets bit 8 of 08.08 Alarm word4.
2056 COOLING FAN
(0x5081)
2057 ADD COOLING
(0x5082)
2058 CABINET FAN
(0x5083)
2059 DC CAPACITOR
(0x5084)
2060 MOTOR BEARING
(0x738C)
2061 MAIN CONTACTOR
(0x548D)
2062 RELAY OUTPUT SW
(0x548E)
2063 MOTOR START COUNT
(0x6180)
2064 POWER UP COUNT
(0x6181)
2065 DC CHARGE COUNT
(0x6182)
2066 ONTIME1 ALARM
(0x5280)
2067 ONTIME2 ALARM
(0x5281)
2068 EDGE1 ALARM
(0x5282)
2069 EDGE2 ALARM
(0x5283)
2070 VALUE1 ALARM
(0x5284)
2071 VALUE2 ALARM
(0x5285)
2072 DC NOT CHARGED
(0x3250)
08.08 Alarm word4 b9
The voltage of the
intermediate DC circuit has
not yet risen to operating
level.
Wait for the DC voltage to rise.
2073 AUTOTUNE FAILED
(0x8481)
08.08 Alarm word4 b10
Speed controller autotune
routine did not finish
successfully.
See parameter 23.20 PI tune mode.
2074 START INTERLOCK
(0xF082)
08.08 Alarm word4 b11
No Start interlock signal
received.
Check circuit connected to DIIL input.
2076 TEMP MEAS FAILURE
(0x4211)
08.08 Alarm word4 b7
Problem with internal
temperature measurement
of the drive.
Contact your local ABB representative.
Code
Alarm (fieldbus code),
other information
Cause What to do