Actual signals and parameters
120
65.07 WEB THICKNESS Set to a value larger than the thickest material that will be run through
the machine. If the value entered is too small, the calculator can not
keep up with the actual rate of change on the machine.
For a wire winding application enter a value equivalent to the wire's
diameter divided by the number of turns needed to complete one full
width of the spool.
0.01…9999.00 mm
0.01…9999.00 mils
Setting range. 100 = 1 mm
100 = 1 mils
65.08 COUNT UP ENABLE Allows the diameter calculator to increase the diameter value.
NO Actual calculated diameter can not increase. 0
YES Actual calculated diameter can increase. 65535
65.09 COUNT DOWN ENABLE Allows the diameter calculator to decrease the diameter value.
NO Actual calculated diameter can not decrease. 0
YES Actual calculated diameter can decrease. 65535
65.10 MAN DIA SLOW RATE Slow rate at which the calculated diameter will change if 65.13 MAN
DIA DEC or 65.12 MAN DIA INC is active. After 3 seconds, the rate
changes to 65.11 MAN DIA FAST RATE.
0.1…1000.0 mm/s
0.1…1000.0 in/s
Setting range. 10 = 1 mm/s
10 = 1 in/s
65.11 MAN DIA FAST RATE Fast rate at which the calculated diameter will change if 65.13 MAN
DIA DEC or 65.12 MAN DIA INC is active.
0.1…1000.0 mm/s
0.1…1000.0 in/s
Setting range. 10 = 1 mm/s
10 = 1 in/s
65.12 MAN DIA INC Sets or selects the activation signal source for manually increasing the
calculated diameter.
NOT SEL Not selected. 1
DI2 Digital input DI2 = 1 increases the calculated diameter at a rate of
65.10 MAN DIA SLOW RATE or 65.11 MAN DIA FAST RATE.
2
DI3 See selection DI2. 3
DI4 See selection DI2. 4
DI5 See selection DI2. 5
DI6 See selection DI2. 6
DI7 See selection DI2. 7
DI8 See selection DI2. 8
DI9 See selection DI2. 9
DI10 See selection DI2. 10
DI11 See selection DI2. 11
DI12 See selection DI2. 12
FIELDBUS See selection DI2. Instead of a digital input, the command comes from
06.03 DATASET 1 WORD 3 bit 09. See chapter Fieldbus control.
13
65.13 MAN DIA DEC Sets or selects the activation signal source for manually decreasing
the calculated diameter.
NOT SEL Not selected. 1
DI2 Digital input DI2 = 1 decreases the calculated diameter at a rate of
65.10 MAN DIA SLOW RATE or 65.11 MAN DIA FAST RATE.
2
DI3 See selection DI2. 3
No. Name/Value Description FbEq