UL
Ordering codeQty
ComponentEnclosure width / Degree of
protection
(Auxiliary voltage)
DataName
3AXD500000061111CRBB/4-400/188Fan
600 mm / IP54
(230vV 50/60 Hz)
3AXD500000068851MSB MKP 12/603/E1679Capacitor
3AXD500000007231SPB2,5/7 (2.5 mm
2
, 12AWG)Connector
3AXD500000007241
SC 2,5-RZ/7 (2.5vmm
2
,
12AWG)
Connector
647500381RH40M-4EK.4I.1RFan
600 mm / IP54
(115 V 50/60 Hz)
68713188125 μF, 220 VCapacitor
3AXD500000007231SPB2,5/7 (2.5 mm
2
, 12AWG)Connector
3AXD500000007241
SC 2,5-RZ/7 (2.5 mm
2
,
12AWG)
Connector
The wiring diagram examples show a cabinet cooling fan circuit that energizes the fan when
at least one inverter module installed in the cabinet is running. The fan will continue to run
for 20 minutes after all inverter modules have been stopped.
The following parts (or equivalent) are used to implement the circuit. These parts are to be
sourced by the customer.
• Phoenix Contact ST 2,5-DIO/L-R - 3036262 spring cage component terminal block with
a 1N4007 diode
• Relpol PI84-24DC-M41G relay
• Rated load (capacity): 8 A / 24 V DC
• Rated power consumption: 0.40 … 0.48 W DC
• GZT80 relay socket
• 600 mm of AWG24, 300 V, UL1569 (or equivalent material, valid for PVC insulation
only) wire
• Favier SEP-4 light brown 4 kV fiberglass sleeving.
■ Cooling fans (frames R6i…R7i)
A cooling fan is to be installed inside the IP54 air outlet compartment to ensure sufficient
cooling of the cabinet.
Ordering codeQty
ComponentEnclosure width / Degree of
protection
(Auxiliary voltage)
DataName
3AXD500000069341RB4C-355/170Fan
400 mm / IP54
(230 V 50/60 Hz)
3AXD500000069591MSB MKP 6/603/E1679Capacitor
3AXD500000007231SPB2,5/7 (2.5 mm
2
, 12AWG)Connector
3AXD500000007241
SC 2,5-RZ/7 (2.5 mm
2
,
12AWG)
Connector
647500621RH35M-4EK.4F.1RFan
400 mm / IP54
(115 V 50/60 Hz)
68713188125vμF, 220 VCapacitor
3AXD500000007231SPB2,5/7 (2.5 mm
2
, 12AWG)Connector
3AXD500000007241
SC 2,5-RZ/7 (2.5 mm
2
,
12AWG)
Connector
272 Ordering information