Standards
See Electrical planning instructions for ACS880 multidrive cabinets and modules
(3AUA0000102324 [English]).
Markings
See Electrical planning instructions for ACS880 multidrive cabinets and modules
(3AUA0000102324 [English]).
Auxiliary power consumptions
■ Control equipment
P
cont
W
I
start
A
I
cont
A
f
Hz
U
N
Device
48-2.0-24 V DC (+10%)ZCU/BCU control unit
105-0.4550/60230 V AC (+15%/-20%)
R8i module: internal electronics
105-0.950/60115 V AC (+15%/-20%)
40--50/60230 V AC
R8i module: heating element
(option +C183)
40--60115 V AC
-3.01.550
400 V AC
R8i module: direct-on-line fan
(option +C188)
-3.81.960
-4.41.560320 V AC
--0.0450/60230 V AC (+10%/-15%)
Charging controller
--0.0850/60115 V AC (+10%/-15%)
6.5--50230 V AC (+10%/-30%)
PDAL2 switch/disconnector inter-
lock coil
6.5--60240 V AC (+10%/-30%)
6.5--60110 V AC (+10%/-30%)
■ Cabinet cooling fans
I
cont
A
f
Hz
U
N
V AC
TypeFrame size
0.750
230R2E225-RA92-17, R3G225-RH17-23
R1i…R5i (IP20/IP42 roof fan) 0.960
1.860115R2E225-BD40-65
1.150
230RB4C-355/170
R1i…R8i (IP54 roof fan)
1.4560
2.350
230CRBB/4-400/188
360
3.150
115RH35M-4EK.4F.1R
3.960
5.550
115RH40M-4EK.4I.1R
6.360
292 Technical data