Frames R1i…R4i Sheet 001 (Main circuit, control unit)
+11.1
=11
=-T11
PEU2 V2 W2
Udc-
Udc+
1PE
NC
NOC
7K
=-F11.1
12
=-F11.2
12
NC
NOC
7K
=-1PE
1PE
INVERTER
MODULE
R1-R4
=-K11
A1A2
12
14 11
14C
=-F11.1
NC
NO C
1D
;F11.2:NC
020/8G
;K11:A2
020/5J
3
4
=-XTE11
1
2
RD10277
=-F11.2
NC
NO C
2D
DC FUSE SUPERVISION
CABINET FAN CONTROL
SEE PAGE 26
X208; 1-2-3
3AXD10000016758 001
020
001.DWG
ACS880-104
INU Frames R1i-R4i
Main Circuit, ZCU-14 Control Unit 1/2
Circuit Diagram
EN
Vanin Oleg29.12.2016
Asikainen Mika29.12.2016
ABB Drives
=-K12
A1A2
=-K13
A1A2
=-K1N
A1A2
12
14 11
12
14 11
12
14 11
=-R12
U1
V1
W1W2
V2
U2
1PE
=-1PE
2PE
PE
=-1PE
2PE
Optional dU/dt filter
MOTOR CONNECTION
DC SWITCH STATUS
FOR INVERTER 1
DC SWITCH STATUS
FOR INVERTER 2
DC SWITCH STATUS
FOR INVERTER 3
DC SWITCH STATUS
FOR INVERTER N
WIRES F11.1/F12.2-T11-R12
R1i 4mm2 BETATHERM
R2i 10mm2 BETATHERM
R3i 16mm2 BETATHERM
R4i 35mm2 BETATHERM
>;DCM:2
>;DCP:2
;12F11.1:1
;12F11.2:1
;13F11.1:1
;13F11.2:1
;14F11.1:1
;14F11.2:1
=-Q11
1
34
2
1314
020/7G
>;DCP:1
>;DCM:1
FROM
SUPPLY
UNIT
TO NEXT
DRIVE UNIT
To Inverter module 2 To Inverter module 3 To Inverter module N
=-K11
12
14 11
8K
-A41
ZCU-14
CONTROL UNIT
MEMORY UNIT
-X205
-XPOW
1 2
+24VDC
11 12 21 22 31 32
RS-485
FOR D2D LINK
-X13
RJ45 FOR PANEL
+VREF
AGND
-XAI
1 2
-VREF
3 4 5 6 7
-XAO
1 2 3 4
DEFAULT OUTPUT DESIGNATION
AO1, AO2; 0(4)...20mA
DEFAULT INPUT DESIGNATION
AI1; 0(2)...10V/-10V...+10V
AI2; 0(4)...20mA
DIIL
-XD24
1 2 3 4
-XRO1
13
-XRO2
23
-XRO3
33
-XDI
1 2 3 4 5 6
DEFAULT INPUT DESIGNATION
DI1...DI6; NOMINAL VOLTAGE 24VDC
-XDIO
1 2
DEFAULT INPUT/OUTPUT DESIGNATION
-SLOT1 -SLOT2
+24V
+24V
+24V
NO
NC
COM
NO
NC
COM
NO
NC
COM
+
-
+
-
RELAY OUTPUT DESIGNATION
RO1...RO3; 250VAC/30VDC, 6A
+
AGND
+
AGND
+24VD
DICOM
+24VD
GND1
21
21
MODULE
CONNECTION
-X201
AI1, AI2 CURRENT/VOLTAGE
SELECTOR JUMPER
JUMPER IN J1A: CURRENT INPUT
JUMPER IN J1B: VOLTAGE INPUT
JUMPER IN J2A: CURRENT INPUT
JUMPER IN J2B: VOLTAGE INPUT
J1B
J1A
AI1
J2B
J2A
AI2
DRIVE-TO-DRIVE LINK
TERMINATION JUMPER
TERMINATED
NOT TERMINATED
(DEFAULT)
5
DIOGND
DI1...DI5
FLOATING POSITION
J6A
-X208
1 2
INT_FAN
3
GND1
INT_FAN_FB
INTERNAL FAN 1
-X210
1 2
INT_FAN
3
GND1
INT_FAN_FB2
INTERNAL FAN 2
-X209
1 2
INAIR_TEMP
GND1
THERMISTOR FOR
INCOMING AIR
10 37 20 20
2 3
-XD2D
1
B
A
BGND
-SLOT3
20
+24V
OUT
SGND
24V DC IN1
IN1
IN2
24V DC IN2
-XSTO
1 2 3 4
SAFETY
OPTION
-X12
20
4
SHIELD
OPTION SLOTS
DICOM CONNECTED
TO DIOGND (DEFAULT)
DICOM FLOATING
J6B
J3
J6A
J6B
-DIO1
11_OUTPUT:RELAY
-DIO2
11_OUTPUT:RUNNING
-DI1
11_START/S TOP
-DI2
11_FORWARD/REVERSE
-DI3
11_RESET
-DI4
0=ACTIVE
11_EMERGENCY STOP
-DI5
1=RUN ENABLED
11_RUN ENABLE
-DI6
11_NOT IN USE
-AO2
0(4)...20mA <-->
0(4)...Motor current
11_CURRENT
-AO1
0(4)...20mA <-->
0(4)...Motor speed
11_SPEED
-AI1
0(2)...10V
11_SPEED REFERENCE
-AI2
By default not in use
0(4)...20mA
11_NOT SPECIFIED
-RO2
1= RUNNING
11_RUNNING
-RO3
1=NO FAULT
11_FAULT (-1)
-RO1
1=ESTOP ACTIVE
11_ESTOP FEEDBACK
+24VDC SUPPLY
SEE PAGE 26
XPOW; 1-2
;A47X1:1
14K
=-A41_MEM
MEMORY
UNIT
R- R+
TERMINATION
SWITCH S1
TERMINATED
OPEN
=-A47
-X100
-X1
-X2
-X3
FDPI-02
DIAGNOSTICS AND PANEL INTERFACE
-DOOR
=-A48
-X100
-X101
-X102
-X103
DPMP-01
PANEL KIT
6
=-A49
X3
USB
CONTROL PANEL
ACS-AP-W
;A47X1:1
D3
384 Circuit diagrams