See section Ratings.
Current
Frames R1i…R4i: 4.5 kHz (typical)Switching frequency
Frames R5i…R8i: 3 kHz (typical)
The switching frequency can vary per frame and voltage. For exact values, please
contact your local ABB representative.
*Frames R1i…R2i: 150 m (492 ft)Maximum recommended
motor cable length
*Frames R3i…R7i: 300 m (984 ft)
Frame R8i and multiples: 500 m (1640 ft)
*Tested with 100 m (328 ft) for EMC Category C3. See standards and markings
information in Electrical planning instructions for ACS880 multidrive cabinets and
modules (3AUA0000102324 [English]).
Note: Longer cables cause a motor voltage decrease which limits the available
motor power. The decrease depends on the motor cable length and characteristics.
Contact ABB for more information. Note that a sine filter (optional) at the drive
output also causes a voltage decrease.
U2, V2, W2: 0.25 … 4 mm
2
, 0.5 … 0.6 N·m (4.4 … 5.3 lbf·in)
Ground: 1.5 N·m (13 lbf·in)
Output terminals (Frame
R1i)
U2, V2, W2: 0.5 … 6 mm
2
, 1.2 … 1.5 N·m (10.6 … 13.3 lbf·in)
Ground: 1.5 N·m (13 lbf·in)
Output terminals (Frame
R2i)
U2, V2, W2: 6 … 70 mm
2
. Allen screw torque 15 N·m (11 lbf·ft), connection post
torque 4 N·m (30 lbf·in). Other conductor sizes can be used by replacing the original
lug with a suitable crimp ring terminal.
Ground: M5, torque 3 N·m (25 lbf·in)
Connector cover screws: Torque 3 N·m (25 lbf·in)
Output terminals
(Frames R3i…R5i)
Output terminals
(Frames R6i and R7i)–
Side view
Screw size: M12 or ½″. Tightening torque: 70 N·m (52 lbf·ft)
288 Technical data