SignificanceDescription
External power input LED can be used to
identify the following status:
No color: External power input
voltage is not in normal range.
Green, solid: External power input
voltage is in normal range.
External power input LED (green)EP
Required test equipment
Equipment needed for troubleshooting.
NoteEquipment
Multimeter
Insulating gloves
3HAC059896-009, 3HAC063898-009,
3HAC072448-009
Circuit diagram - OmniCore C30, Circuit dia-
gram - OmniCore C30 for IRB 14050, Circuit
diagram - OmniCore C30 for CRB 15000
Preparations
Action
Check the FlexPendant for errors and warnings.1
Power the controller off. Wait one minute, power the controller on.2
Wait 30-60 seconds after power-on.3
Make sure that the control system power is in run-time mode.
Continues on next page
558 Product manual - OmniCore C30
3HAC060860-001 Revision: P