Detailed working procedure
NoteAction
Make sure that the mains switch (Q0) has been
switched on.
1
Use a multimeter and insulating
gloves.
Make sure that the system is supplied with power.
Measure incoming mains voltage and make
sure the voltage is within the normal range.
2
If incoming mains is not ok, the
problem is not in the robot control-
ler. Troubleshoot incoming mains.
Check that the mains connection (X0) is properly
connected.
Tip
For more details, see Circuit diagram - OmniCore
V250XT, rev 04 or later.
3
Check that the AC input cable is properly connec-
ted.
4
Use a multimeter and insulating
gloves.
Check the output voltage of (Q0).
Make sure that (Q0) is closed.
5
Replace if damaged.Check the fuse (F1).6
If abnormal, troubleshoot
the power unit. See
Troubleshooting the power
unit on page 383.
Check connector A1.X1.7
If abnormal, troubleshoot
the LEDs. See
Troubleshooting LEDs in the
controller on page 368.
Check the LED status.8
350 Product manual - OmniCore V250XT Type B
3HAC087112-001 Revision: A
© Copyright 2023-2023 ABB. All rights reserved.
7 Troubleshooting
7.2.1 No LEDs are lit on the controller
Continued

Table of Contents