EasyManua.ls Logo

ABB OmniCore V250XT Type B - Page 392

ABB OmniCore V250XT Type B
468 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DescriptionName
The status indicator LED can be used to identify the
following status during startup/power on:
Red, steady: Default when power is available.
Red, flashing (~1Hz): Power is on, self-test is
ongoing, operating system is loading.
Green, flashing (~1Hz): Application is loaded
and waiting for communication.
Green, steady: Unit is operational.
If the LED does not turn steady green after 30-60 sec,
the status indicator LED can be used to identify the
following issues:
No color: Power to the power unit is missing.
Red, steady: Internal error.
Red, flashing (~1Hz): Firmware error or self-test
failure.
Green, flashing (~1Hz): Communication error
to another module.
Green, steady: Unit is operational.
Module Status
Required test equipment
Equipment needed for troubleshooting:
NoteEquipment
Multimeter
Insulating gloves
3HAC074000-008Circuit diagram - OmniCore V250XT, rev 04
or later
Preparations
Action
Check the FlexPendant for errors and warnings.1
Power the controller off. Wait one minute, power the controller on.2
Wait 30-60 seconds after power-on.3
Make sure that the control system power is in run-time mode.
Continues on next page
392 Product manual - OmniCore V250XT Type B
3HAC087112-001 Revision: A
© Copyright 2023-2023 ABB. All rights reserved.
7 Troubleshooting
7.3.6 Troubleshooting the HVLP power unit (DSQC3072)
Continued

Table of Contents

Related product manuals