Parameters 99
BACnet/IP 47808
Ethernet/IP 2222
Modbus/TCP 502
154.02 FBA Par2 Parameters 154.02…154.26 are adapter module-
specific. For more information, see the documentation of
fieldbus adapter module. Note that not all of these
parameters are necessarily in use.
-/ Real
0...65535 1 = 1
... ... … …
154.26 FBA Par26 See parameter 154.02 FBA Par2. -/ Real
0...65535 1 = 1
154.27 FBA par refresh Validates any changed fieldbus adapter module
configuration settings. After refreshing, the value reverts
automatically to Done.
Note: This parameter cannot be changed while the
inverter is running.
Done/ List
Done Refreshing done. 0
Configure Refreshing. 1
154.28 Par table ver Shows parameter table revision of the fieldbus adapter
module mapping file stored in the inverter memory in
format axyz, where
a = major revision number
xy = minor revision number
z = correction number.
This parameter is read-only.
-/ Data
154.29 Drive type code Shows the inverter type code of the fieldbus adapter
module mapping file stored in the memory of the
inverter.
This parameter is read-only.
-/ Real
0...65535 I type code of fieldbus adapter module mapping file. 1 = 1
154.30 Mapping file ver Shows fieldbus adapter module mapping file revision
stored in the memory of the inverter in decimal format.
Example: Integer 263 -> 0x107 = revision 1.07
This parameter is read-only.
-/ Real
0...65535 Mapping file revision. 1 = 1
154.31 D2FBA comm sta Shows the status of fieldbus adapter module
communication.
Idle/ List
Idle Adapter is not configured. 0
Exec.init Adapter is initializing. 1
Time out A timeout has occurred in the communication between
adapter and inverter.
2
Conf.err Adapter configuration error: The major or minor revision
code of the common program revision in the fieldbus
adapter module is not the revision required by the
module (see parameter 51.32 FBA comm sw ver) or
mapping file upload has failed more than three times.
3
Off-line Adapter is off-line. 4
On-line Adapter is on-line. 5
Reset Adapter is performing a hardware reset. 6
No. Name/Value Description Def/
FbEq16/32