158 Troubleshooting
28187
(0x6e1b)
Backup/Restore
Timeout
Parameter backup/Restore
timeout error detected.
Check panel / PC-tool
connection and retry
Backup/Restore, if problem
persists contact your local
FIMER representative.
28188
(0x6e1c)
Fast power off Inverter has received a fast
power off command.
1. Check that it is safe to
continue operation.
2. Return fast power off
pushbutton to normal position.
3. Restart inverter.
32257
(0x7e01)
Panel loss Control panel loss fault detected.
Control panel or PC tool selected
as active control location for
inverter has stopped
communicating.
Check:
PC tool or control panel
connection
control panel connector.
Replace control panel in
mounting platform.
32266
(0x7e0a)
Overfrequency Gridmonitoring frequency
exceeded limits.
Reset fault when grid situation
has stabilized.
32267
(0x7e0b)
FBA A communication Fieldbus adapter module A
communication fault.
Cyclical communication between
inverter and fieldbus adapter
module A or between PLC and
fieldbus adapter module A is lost.
Check:
status of field bus
communication. See user
documentation of fieldbus
interface
settings of parameter groups:
150 FBA, 151 FBA A settings,
152 FBA A data in and 153
FBA A data out
cable connections
communication master is able
to communicate.
32268
(0x7e0c)
FBA B communication Fieldbus adapter B
communication fault.
Cyclical communication between
inverter and fieldbus adapter
module B or between PLC and
fieldbus adapter module A is lost.
Check:
status of fieldbus
communication. See user
documentation of fieldbus
interface.
settings of parameter groups:
150 FBA, 154 FBA B settings,
155 FBA B data in and 156
FBA B data out.
cable connections
communication master is able
to communicate.
Code in
Dec
(Hex)
Fault Cause What to do