Parameters 75
126.15 Lv Rt sec 4 time Defines duration of low voltage tripping curve (Lv Rt)
section 4. If duration is greater than zero, the Lv Rt
section is enabled.
600 ms/ Real
0 … 300000 ms Low voltage tripping curve section 4 duration. 1 = 1 ms
126.16 Lv Rt sec 5 time Defines duration of low voltage tripping curve (Lv Rt)
section 5. If duration is greater than zero, the Lv Rt
section is enabled.
600 ms/ Real
0 … 300000 ms Low voltage tripping curve section 5 duration. 1 = 1 ms
126.17 Lv Rt ext time Defines extended duration of low voltage tripping curve
(Lv Rt) section. If duration is greater than zero, the
extended Lv Rt section is enabled. This kind of extended
section is required for a few grid codes.
0 ms/ Real
0 … 300000 ms Low voltage tripping curve section extended duration. 1 = 1 ms
126.18 Lv Rt S1 start U % Defines starting voltage level of section 1. 0%/ Real
0 … 100% Starting voltage level of section 1. 1 = 1%
126.19 Lv Rt S1 end U % Defines final voltage level of section 1. 0%/ Real
0 … 100% Final voltage level of section 1. 1 = 1%
126.20 Lv Rt S2 start U % Defines starting voltage level of section 2. 0%/ Real
0 … 100% Starting voltage level of section 2. 1 = 1%
126.21 Lv Rt S2 end U % Defines final voltage level of section 2. 20%/ Real
0 … 100% Final voltage level of section 2. 1 = 1%
126.22 Lv Rt S3 start U % Defines starting voltage level of section 3. 20%/ Real
0 … 100% Starting voltage level of the section 3. 1 = 1%
126.23 Lv Rt S3 end U % Defines final voltage level of section 3. 40%/ Real
0 … 100% Final voltage level of section 3 1 = 1%
126.24 Lv Rt S4 start U % Defines starting voltage level of section 4. 40%/ Real
0 … 100% Starting voltage level of section 4. 1 = 1%
126.25 Lv Rt S4 end U % Defines final voltage level of section 4. 60%/ Real
0 … 100% Final voltage level of section 4. 1 = 1%
126.26 Lv Rt S5 start U % Defines starting voltage level of section 5. 60%/ Real
0 … 100% Starting voltage level of section 5. 1 = 1%
126.27 Lv Rt S5 end U % Defines final voltage level of section 5. 80%/ Real
0 … 100% Final voltage level of section 5. 1 = 1%
126.28 Lv Rt ext U % Defines voltage level of extended section. The extended
section is required in some grid codes.
80%/ Real
0 … 100% Voltage level of extended section. 1 = 1%
126.30 Hv Rt trig U % Activates high voltage tripping curve function when
mains voltage is above the trigger level.
115%/ Real
0 … 150% High voltage tripping curve function trigger level. 1 = 1%
126.31 Hv Rt recover hyst U % Defines high voltage tripping curve function recover
hysteresis. The curve is deactivated when the mains
voltage is below the trigger limit minus hysteresis.
5%/ Real
0 … 20% High voltage tripping curve function recover hysteresis. 1 = 1%
126.32 Hv Rt sec 1 time Defines duration of high voltage tripping curve (Hv Rt)
section 1. If duration is greater than zero, the low
voltage tripping curve (Lv Rt) section is enabled.
100 ms/ Real
0 … 5000 ms High voltage tripping curve section 1 duration. 1 = 1 ms
No. Name/Value Description Def/
FbEq16/32

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB PVS980-58 and is the answer not in the manual?

ABB PVS980-58 Specifications

General IconGeneral
BrandABB
ModelPVS980-58
CategoryInverter
LanguageEnglish

Related product manuals