84 Parameters
135.52 Undervoltage time 1 Defines tripping time for undervoltage condition 1. 200 ms/ Real
100...600000 ms Undervoltage condition 1 trip time. 1 = 1 ms
135.53 Undervoltage enable 2 Enables undervoltage condition 2. 1/ Real
0...1 0 - Undervoltage condition 2 is disabled.
1 - Undervoltage condition 2 is enabled.
1 = 1
135.54 Undervoltage limit 2 Defines limit for undervoltage condition 2. 80 %/ Real
0...100 % Undervoltage condition 2 limit. 1 = 1 %
135.55 Undervoltage time 2 Defines tripping time for undervoltage condition 2. 500 ms/ Real
100...600000 ms Undervoltage condition 2 trip time. 1 = 1 ms
135.56 Undervoltage enable 3 Enables undervoltage condition 3. 0 / Real
0...1 0 - Undervoltage condition 3 disabled.
1 - Undervoltage condition 3 enabled.
1 = 1
135.57 Undervoltage limit 3 Defines limit for undervoltage condition 3. 80 %/ Real
0...100 % Undervoltage condition 3 limit. 1 = 1 %
135.58 Undervoltage time 3 Defines tripping time for undervoltage condition 3. 100 ms/ Real
100...600000 ms Undervoltage condition 3 trip time. 1 = 1 ms
135.59 Undervoltage enable 4 Enables undervoltage condition 4. 0 / Real
0...1 0 - Undervoltage condition 4 disabled.
1 - Undervoltage condition 4 enabled.
1 = 1
135.60 Undervoltage limit 4 Defines limit for undervoltage condition 4. 80 %/ Real
0...100 % Undervoltage condition 4 limit. 1 = 1 %
135.61 Undervoltage time 4 Defines tripping time for undervoltage condition 4. 100 ms/ Real
100...600000 ms Undervoltage condition 4 trip time. 1 = 1 ms
135.63 Overvoltage enable 1 Enables overvoltage protection 1. 1 / Real
0...1 0 - Overvoltage protection 1 disabled.
1 - Overvoltage protection 1 enabled.
1 = 1
135.64 Overvoltage limit 1 Defines limit for overvoltage protection 1. 120 %/ Real
100...200 % Overvoltage protection 1 limit. 1 = 1 %
135.65 Overvoltage time 1 Defines trip time for overvoltage protection 1. 0 ms/ Real
100...600000 ms Overvoltage protection 1 trip time. 1 = 1 ms
135.66 Overvoltage enable 2 Enables overvoltage protection 2. 1/ Real
0...1 0 - Overvoltage protection 2 disabled.
1 - Overvoltage protection 2 enabled.
1 = 1
135.67 Overvoltage limit 2 Defines limit for overvoltage protection 2. 115 %/ Real
100...200 % Overvoltage protection 2 limit. 1 = 1 %
135.68 Overvoltage time 2 Defines trip time for overvoltage protection 2. 1000 ms/
Real
100...660000 ms Overvoltage protection 2 trip time. 1 = 1 ms
135.69 Overvoltage enable 3 Enables overvoltage protection 3. 0/ Real
0...1 0 - Overvoltage protection 3 disabled.
1 - Overvoltage protection 3 enabled.
1 = 1
135.70 Overvoltage limit 3 Defines limit for overvoltage protection 3. 130 %/ Real
100...200 % Overvoltage protection 3 limit. 1 = 1 %
135.71 Overvoltage time 3 Defines trip time for overvoltage protection 3. 100 ms/ Real
100...600000 ms Overvoltage protection 3 trip time. 1 = 1 ms
No. Name/Value Description Def/
FbEq16/32