EasyManua.ls Logo

ABB REL650 - Page 110

ABB REL650
942 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21LL
U
12
1
L L set
IZ
setLLLLcomp
ZIUU 1
2121
pol
U
jXI
LL
21
RI
LL
21
IEC15000060-1-en.vsdx
IEC15000060 V1 EN-US
Figure 37: Simplified mho characteristic and vector diagram for phase L1-to-
L2 fault
Offset Mho
GUID-3E13E6D5-0832-4386-9677-9A40BFF42F8F v2
The characteristic for offset mho is a circle with origin as the center and magnitude
of
Z set1
as the radius, where
Z set1
is settable through the resistance and reactance
settings.
The condition for operation at phase-to-phase fault is that the angle β between the
two compensated voltages is greater than or equal to 90° (figure
38). The angle will
be 90° for fault location on the boundary of the circle.
The angle β for L1 to L2 fault can be defined according to equation below.

12 12
12 12
1
arg
1
LL LL set
LL LL set
UIZ
UIZ






IECEQUATION15008 V2 EN-US (Equation 6)
Section 6 1MRK 506 382-UEN A
Impedance protection
104 Line distance protection REL650 2.2 IEC
Technical manual

Table of Contents

Other manuals for ABB REL650

Related product manuals