GUID-D6B3DFE3-F7DF-4602-B57E-764DC9EB0D4A v1
Table 275: SMPPTRC Output signals
Name Type Description
TRIP BOOLEAN General trip output signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TR1P BOOLEAN Trip single-pole
TR2P BOOLEAN Trip two-pole
TR3P BOOLEAN Trip three-pole
CLLKOUT BOOLEAN Circuit breaker lockout output (set until reset)
START BOOLEAN General start signal
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STN BOOLEAN Start signal from neutral
FW BOOLEAN General forward signal
REV BOOLEAN General reverse signal
13.1.5 Settings
GUID-6D6424B9-B676-4D9B-949A-33C74BDC5711 v1
Table 276: SMPPTRC Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
Program 3 phase
1ph/3ph
1ph/2ph/3ph
-
- 1ph/3ph Three ph; single or three ph; single, two
or three ph trip
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signal
tWaitForPHS 0.020 - 0.500 s 0.001 0.050 Secure 3-pole trip when phase selection
failed
Table 277: SMPPTRC Group settings (advanced)
Name
Values (Range) Unit Step Default Description
TripLockout Off
On
- - Off Latch TRIP output when SETLKOUT
input is activated
AutoLock Off
On
- - Off Activate CLLKOUT output when TRIP
output is activated
tEvolvingFault 0.000 - 60.000 s 0.001 2.000 Secure 3-pole tripping at evolving faults
1MRK 506 382-UEN A Section 13
Logic
Line distance protection REL650 2.2 IEC 465