Name Type Values (Range) Unit Description
UnTrigStatCh40 BOOLEAN - - Under level trig for
analog channel 40
activated
OvTrigStatCh40
BOOLEAN - - Over level trig for analog
channel 40 activated
FaultNumber INTEGER - - Disturbance fault
number
14.6.7 Operation principle
M12155-6 v10
Disturbance report DRPRDRE is a common name for several functions to supply
the operator, analysis engineer, and so on, with sufficient information about events
in the system.
The functions included in the disturbance report are:
Event list (EL)
Indications (IND)
Event recorder (ER)
Trip value recorder (TVR)
Disturbance recorder (DR)
Fault locator (FL)
Settings information
Figure
308 shows the relations between Disturbance Report, included functions
and function blocks. Event list (EL), Event recorder (ER) and Indications (IND)
uses information from the binary input function blocks (BxRBDR). Trip value
recorder (TVR) uses analog information from the analog input function blocks
(AxRADR) which is used by FL after estimation by TVR. Disturbance recorder
DRPRDRE acquires information from both AxRADR and BxRBDR.
1MRK 506 382-UEN A Section 14
Monitoring
Line distance protection REL650 2.2 IEC 609
Technical manual