Soft ground connector pinouts
SEMOD158670-45 v1
A second 2-pole screw connector is used for the connection of IO-ground. It can be
used in two combinations like:
Unconnected: No ground of the IO-part · .
Soft grounded: The IO is connected to the GND with an RC net parallel with a
MOV
20.2.11.3 Technical data
SEMOD158678-1 v1
SEMOD158710-2 v2
Table 656: Galvanic RS485 communication module
Quantity Range or value
Communication speed 2400–19200 bauds
External connectors RS-485 6-pole connector
Soft ground 2-pole connector
20.2.12 IRIG-B time synchronization module IRIG-B
SEMOD141102-1 v1
20.2.12.1 Introduction
SEMOD141113-4 v8
The IRIG-B time synchronizing module is used for accurate time synchronizing of
the IED from a station clock.
The precision time protocol (PTP, IEC/IEEE 61850-9-3) input shall be used for
synchronizing when IEC/UCA 61850-9-2LE is used.
Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support.
20.2.12.2 Design
SEMOD141098-4 v4
The IRIG-B module has two inputs. One input is for the IRIG-B that can handle
both a pulse-width modulated signal (also called unmodulated) and an amplitude
modulated signal (also called sine wave modulated). The other is an optical input
type ST for optical pulse-width modulated signal (IRIG-B 00X). The IRIG-B
module is mounted as a mezzanine card on the Analog digital conversion module
(ADM).
Section 20 1MRK 506 382-UEN A
IED hardware
864 Line distance protection REL650 2.2 IEC
Technical manual