11.1.3 Function block
M12431-3 v7
SESRSYN
U3PBB1*
U3PBB2*
U3PLN1*
U3PLN2*
BLOCK
BLKSYNCH
BLKSC
BLKENERG
B1QOPEN
B1QCLD
B2QOPEN
B2QCLD
LN1QOPEN
LN1QCLD
LN2QOPEN
LN2QCLD
UB1OK
UB1FF
UB2OK
UB2FF
ULN1OK
ULN1FF
ULN2OK
ULN2FF
STARTSYN
TSTSYNCH
TSTSC
TSTENERG
AENMODE
MENMODE
SYNOK
AUTOSYOK
AUTOENOK
MANSYOK
MANENOK
TSTSYNOK
TSTAUTSY
TSTMANSY
TSTENOK
USELFAIL
B1SEL
B2SEL
LN1SEL
LN2SEL
SYNPROGR
SYNFAIL
UOKSYN
UDIFFSYN
FRDIFSYN
FRDIFFOK
FRDERIVA
UOKSC
UDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
INADVCLS
UDIFFME
FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN
IEC10000046-1-en.vsd
IEC10000046 V1 EN-US
Figure 166: SESRSYN function block
11.1.4 Signals
PID-6724-INPUTSIGNALS v1
Table 188: SESRSYN Input signals
Name
Type Default Description
U3PBB1 GROUP
SIGNAL
- Group signal for phase to earth voltage input L1,
busbar 1
U3PBB2 GROUP
SIGNAL
- Group signal for phase to earth voltage input L1,
busbar 2
U3PLN1 GROUP
SIGNAL
- Group signal for phase to earth voltage input L1,
line 1
U3PLN2 GROUP
SIGNAL
- Group signal for phase to earth voltage input L1,
line 2
BLOCK BOOLEAN 0 General block
BLKSYNCH BOOLEAN 0 Block synchronizing
BLKSC BOOLEAN 0 Block synchro check
BLKENERG BOOLEAN 0 Block energizing check
Table continues on next page
Section 11 1MRK 506 382-UEN A
Control
334 Line distance protection REL650 2.2 IEC
Technical manual

Table of Contents

Other manuals for ABB REL650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REL650 and is the answer not in the manual?

ABB REL650 Specifications

General IconGeneral
BrandABB
ModelREL650
CategoryProtection Device
LanguageEnglish

Related product manuals